Dräger Flame 1350 UV/IR Flame Detector
The Dräger Flame 1350 is a UV/IR flame detector that combines ultraviolet (UV) and infrared (IR) sensing technology to provide fast and reliable detection of hydrocarbon fires. Advanced detection algorithms and dual-sensor technology help minimise false alarms while ensuring dependable performance in hazardous environments.
Features
- Combined UV and IR flame detection technology.
- Designed for hydrocarbon fire detection.
- SIL2 certified to IEC 61508.
- Complies with EN54-10 and FM3260 performance standards.
- HART and RS-485 communication interfaces.
- Low power consumption.
- Advanced Optical Verification (AOV) self-test.
- Automatic heated window to prevent icing and condensation.
- Operating temperature range from -60°C to +85°C.
- Tri-colour LED status indicator.
- Available in aluminium and stainless steel housings.
- Configurable as UV/IR, UV-only, or IR-only detector.
Benefits
- Fast and reliable flame detection.
- Excellent immunity to false alarms.
- Automatic monitoring of optics and electronics.
- Reliable performance in harsh industrial environments.
- Flexible configuration for different fire detection applications.
Status Indicators
- Green LED – Normal operation.
- Yellow LED – Fault condition.
- Red LED – Fire alarm.
Order Information
- 3724443 – Dräger Flame 1350, Aluminium, 2 × M25.
- 3724441 – Dräger Flame 1350, Aluminium, 2 × 3/4" NPT.
- 3724442 – Dräger Flame 1350, Stainless Steel, 2 × M25.
- 3724440 – Dräger Flame 1350, Stainless Steel, 2 × 3/4" NPT.
Accessories
- 4209307 – Dräger FS-5000 Flame Simulator.
- 3718732 – Standard Swivel Mount (316 Stainless Steel).
- 3701298 – Marine Swivel Mount (316 Stainless Steel).
- 3701303 – Density Set Detector (Metric).
- 3701299 – Sun Protection Shield.
- 3701300 – 2" Pole Mount Clamp.
- 3701301 – 3" Pole Mount Clamp.
- 3701302 – 4" Pole Mount Clamp.
- 3724460 – Air Shield for Stainless Steel Flame Detectors.
- 3724461 – Air Shield for Aluminium Flame Detectors.
- 3724462 – Duct Mount (Stainless Steel).
- 3724463 – Adaptor Bracket (Stainless Steel).
- 3724464 – USB HART Modem.
- 3724465 – Charger for FS-5000 Flame Simulator.
- 3724466 – USB to RS-485 Converter.
Detector Characteristics
| Parameter |
Specification |
| Model |
Dräger Flame 1350 |
| Type |
Explosion-proof UV/IR flame detector |
| Spectral Range |
0.18 to 0.2 µm and 3 to 5 µm |
| Field of View |
Horizontal: 90° Vertical: 90° |
| Response Time |
5 seconds (typical) |
| Sensitivity Settings |
Low (10 m), Standard (20 m) and High (30 m) |
Detection Range
| Fuel |
Range |
| n-Heptane / Petrol |
30 m (100 ft) |
Note: Detection range based on a 0.1 m² (1 ft²) fire pan or a 0.6 m (3 ft) flare.
Electrical Specifications
| Parameter |
Specification |
| Relay Outputs |
Alarm and Fault |
| Signal Output |
0–20 mA |
| Communication |
RS485, HART® 7 |
| Supply Voltage |
24 VDC nominal (18–32 VDC) |
| Power Consumption |
Minimum 3 W / Maximum 12 W with heating |
Mechanical Specifications
| Parameter |
Specification |
| Housing Material |
Aluminium or Stainless Steel, powder-coated |
| Cable Entry |
Dual M25 or ¾″ NPT |
| Weight |
Aluminium: 2.5 kg (5.5 lbs) Stainless Steel: 6 kg (13.2 lbs) |
| Protection Rating |
IP66, NEMA 4X |
Environmental Conditions
| Parameter |
Specification |
| Operating Temperature |
-60°C to +85°C (-76°F to +185°F) |
Approvals & Certifications
| Certification |
Approval |
| ATEX |
Ex II 2 G Ex db IIC T4 Gb IP66 |
| IECEx |
Ex II 2 G Ex db IIC T4 Gb IP66 |
| FM/FMC |
Class 1 Zone 1 AEx db IIC T4 Class 1 Div. 1, Groups B, C, D T4 |
| EAC TR CU |
Pending |
| CCCF |
Pending |
| INMETRO / PESO |
Available on request |
| Functional Safety |
SIL2 (IEC 61508-1-3) |
| Performance Certification |
EN 54-10 (VdS) |