Drager Flame 1300 Flame Detector

  1. Home
  2. Products

Dräger Flame 1300 IR Flame Detector

The Dräger Flame 1300 is an infrared (IR) flame detector designed to detect hydrocarbon fuels, vapours, and other organic-based fires. It provides reliable fire detection with excellent immunity to false alarms and offers flexible output options for a wide range of industrial applications.

Note: This product is obsolete. The nearest equivalent replacement is the Dräger Flame 1500.

Features

  • Infrared (IR) flame detection technology.
  • Detects hydrocarbon fuels and vapours.
  • Simple installation with adjustable stainless steel mounting bracket.
  • Angular markings for accurate detector positioning.
  • 4–20 mA output as standard.
  • Three programmable relay outputs.
  • Optional RS-485 communication.
  • Automatic and manual optics self-test.
  • Operates as either a three-wire or four-wire device.
  • Tri-colour status LED for easy status indication.
  • Excellent immunity to false alarms.
  • Available in aluminium and stainless steel housings.

Status Indicators

  • Green LED – Normal operation.
  • Yellow LED – Fault condition.
  • Red LED – Flame detected.

Approvals

  • ATEX Certified.
  • IECEx Certified.
  • FM Approved.
  • CSA Approved.

Order Information

  • 2350422 – Dräger Flame 1300, Aluminium Housing, M20 Entries.
  • 2350429 – Dräger Flame 1300, Aluminium Housing, M25 Entries.
  • 2350435 – Dräger Flame 1300, Aluminium Housing, 1/2" NPT Entries.
  • 2350441 – Dräger Flame 1300, Aluminium Housing, 3/4" NPT Entries.
  • 2350425 – Dräger Flame 1300, Stainless Steel Housing, M20 Entries.
  • 2350432 – Dräger Flame 1300, Stainless Steel Housing, M25 Entries.
  • 2350438 – Dräger Flame 1300, Stainless Steel Housing, 1/2" NPT Entries.
  • 2350444 – Dräger Flame 1300, Stainless Steel Housing, 3/4" NPT Entries.
Specification Details
Type Explosion proof IR flame detector for hydrocarbon based fires
Spectral response 4.2 to 4.7 micron
Field of view Horizontal 90°, Vertical 90°
Sensitivity 0.1 m² gasoline fire at 18 metres, 1 sq. foot fire at 60 feet
Response time (t90) 3.5 seconds typical, configurable up to 30 seconds
Signal output Fault: 0 mA
Optics/electronics check failure: 2 mA
Normal operation: 4 mA
Fire pre-warning: 16 mA
Fire: 20 mA (factory configurable for latching/non-latching alarm)

3 relays for fault, alarm and accessory (125 VAC, 0.5 A; 30 VDC, 2 A)
Optional RS-485
Supply voltage 18 to 32 VDC, current consumption 160 mA (quiescent state at 24 VDC)
Ambient conditions Temperature: –40 to +70 °C (–40 to +158 °F)
Pressure: 915 to 1055 hPa (27.9 to 31.2 inch Hg)
Humidity: 0 to 99% RH, non-condensing
Enclosure IP66 / NEMA 4X
Cable entry M20, M25, 1/2” NPT or 3/4” NPT
Size (L × D, approx.) 275 × 155 mm (10.8 × 6.1 inches)
Weight (approx.) 3.5 kg (7.7 lbs)
Approvals ATEX II 2G EEx d IIC T6/T5; –50 ≤ Tamb ≤ +60 / +70 °C
IECEx Ex d IIC T6/T5; –50 ≤ Tamb ≤ +60 / +70 °C
FM/CSA Class I, Groups A, B, C, D, Class I, Zone 1, Groups IIA, IIB & IIC, Ex d IIC; T6/T5; –40 ≤ Tamb ≤ +60 / +70 °C