The Crowcon FGard IR3 is a multi-spectrum infrared (IR3) flame detector designed to provide fast and reliable detection of hydrocarbon liquid fuel and gas fires. It combines advanced flame detection algorithms, heated optics, and automatic optical verification to deliver excellent false alarm immunity.
| Specification | Details |
|---|---|
| Operating temperature | -60°C to +85°C (-76°F to +185°F) |
| Storage temperature | -76°F to +185°F (-60°C to +85°C) |
| Humidity | 0-100% RH (Non-condensing) |
| Operating voltage | 24 VDC Nominal (Range: 18 to 32 VDC) |
| Power consumption | 3 W minimum (without heater), 15 W at 32 VDC with heater on maximum |
| Speed of response | < 5 seconds (Typical) |
| Dimensions | 100 mm Dia × 200 mm (4” Dia × 8” L) |
| Material | Copper free aluminum or 316 stainless steel |
| Entry size | 3/4 inch NPT or M25 |
| Weight | Aluminum: 5.5 lbs (2.5 kg) / Stainless Steel: 13.2 lbs (6.0 kg) |
| Outputs |
Relay contacts (DPDT 2A at 30 VDC) – Alarm and Fault 0-20 mA plus fault alerts, HART® |
| Certifications |
Class 1 Div 1 Groups B, C, D T4 Ambient –50°C to +85°C Class 1 Zone 1 AEx/Ex db IIC T4 Ambient –50°C to +85°C ATEX II 2 G Ex db IIC T4 IECEx Ex db IIC T4 Ambient –60°C to +85°C INMETRO Ex db IIC T4 PESO Ex db IIC T4 Ta = -60°C to +85°C CCC (China Fire Approvals) – Pending GB-Ex of China – Pending |
| Performance approvals |
FM 3260 EN 54-10 Ingress: IP66 / NEMA 4X SIL2 – IEC 61508 |
Get in touch with us to see how we can help you with your project