The S4000TH is obsolete and has been replaced by the S5000 Gas Monitor, which offers enhanced performance and advanced features for H2S detection. The mounting footprint and cable entries of the two transmitters are identical, which makes retrofitting simple. To help with the transition to the latest technology, please refer to the white paper.
The S4000TH Intelligent Sensor is a microprocessor-based transmitter designed for use with General Monitors’ Metal Oxide Semiconductor (MOS) sensor. This unit features one-person calibration and can virtually self-calibrate by simply activating a magnetic switch and applying gas. It is designed to detect hydrogen sulfide in parts per million (ppm) levels and provide status indication and alarm outputs.
All of the S4000TH electronics are contained within an explosion-proof housing, allowing sensor information to be processed at the sensor site. It provides a 4-20 mA signal that is proportional to 0-100% of the sensor’s detection range. In addition, the S4000TH includes warning, alarm, and fault relay contacts that can be used to indicate an alarm or fault condition, as well as dual redundant Modbus or HART communications. Configurations with relays, Modbus and HART are available to meet many needs.
The S4000TH includes a three (3) digit LED display. This local digital display continuously indicates gas concentrations during normal operation and in calibration check mode, as well as prompts during calibration mode, displays codes during setup mode, and eight fault codes. The S4000TH has four different operating modes.
First, the normal operating mode in which alarms are active and the display and 4-20 mA readings are proportional to the gas concentration at the sensor. Second, the gas check mode enables the user to apply gas and verify the sensor response while alarm outputs are inhibited. Third, a calibration mode in which gas is applied to the sensor to calibrate the unit. Finally, a setup mode is available that allows users to review and modify setup options, including relay settings, sensor range, and Modbus parameters. Selecting Setup Mode on the S4000TH is accomplished by using the magnetic switch, HART or Modbus command.
| System Specifications | |
|---|---|
| Sensor Type | Continuous diffusion, adsorption type Metal Oxide Semiconductor (MOS) |
| Sensor Life | 3 to 5 years typical |
| Repeatability | ±2 ppm or 10% of the applied gas, whichever is greater |
| Response Time |
T50 < 14 seconds (screen) T50 < 30 seconds (sintered) With full scale gas applied according to ISA 92.0.01 |
| Measuring Ranges | 0-20 ppm, 0-50 ppm, 0-100 ppm |
| Modes | Calibration, calibration check, setup |
| Classification | |
| CSA/FM |
Class I, Division 1, Groups B, C & D; T6 (Tamb = -40°C to +75°C)-CSA (Tamb = -40°C to +60°C)-FM |
| CSA |
Ex db IIB + H2 T4 Gb (Tamb=-40°C to +70°C); Ex tb IIIC T135°C Db |
| ATEX/IECEX |
II 2 GD Ex db IIB+H2, T4 Gb, Ex tb IIIC T135°C Db (Tamb = -40°C to +70°C) |
| Warranty | Two years |
| Approvals |
ATEX, CSA, FM, IECEx, EAC, CE Mark, HART registered, SIL 2 and 3
suitable*, FM certiQed to IEC 61508 |
| Environmental Specifications | |
| Operating Temperature Range (ELECTRONICS) |
-40°F to 167°F (-40°C to 75°C) – CSA (div.) -40°F to 158°F (-40°C to +70°C) – CSA (zone) -40°F to 140°F (-40°C to +60°C) – FM -40°F to 158°F (-40°C to +70°C) – ATEX/IECEx |
| Storage Temperature Range | -58°F to 185°F (-50°C to 85°C) |
| Operating Humidity Range | 0% to 95% RH, non-condensing |
| Mechanical Specifications | |
| Length | 6.4 inches (161 mm) |
| Height | 3.4 inches (86 mm) |
| Width | 4.1 inches (104 mm) |
| Weight | 5.5 lbs. (2.5 kg) – AL, 14.0 lbs. (6.4kg) – SS |
| Mounting Holes | 5.0 inches (127 mm) (center to center) |
| Housing |
Aluminum 6061-T6 alloy (cover), A356-T6 alloy (base) or 316 Stainless Steel |
| Electrical Specifications | |
| Input Power |
24 VDC nominal, 20 to 36 VDC 350 mA max. |
| Power Consumption |
270 mA (start-up) 120 mA (normal) |
| Relay Ratings OPTIONAL |
8A @ 250 VAC / 8A @ 30 VDC res. max. (3x) SPDT – Warning, Alarm & Fault |
| Analog Signal | 0-20 mA (650 Ohms max. load) |
| EMC Protection | Complies with EN 50270, EN 61000-6-4 |
| Status Indicators | Three-digit LED display with gas concentration, Warn and Alarm LED’s, calibration prompts, fault codes, and setup options |
| RS8485 Output (Optional) | Dual redundant Modbus RTU, suitable for linking up to 128 units or up to 247 units with repeaters |
| Baud Rate | 2400, 4800, 9600, or 19200 BPS |
| HART (Optional) | RX 100K, CS 5nF |
| Faults Monitored | Calibration error, sensor heater error, low DC supply, EEPROM, EPROM, setup error, gas check time exceeded, switch error, magnet errors |
| Cable Requirements | 3 wire shielded cable. Max. distance between S4000TH and power source or remote sensor |