The IR400 Infrared (IR) Point Detector is a hydrocarbon gas detector that continuously monitors combustible gases and vapours within the lower explosive limit (LEL) and provides alarm indication.
It features an industry-leading response time of less than 3 seconds, even with a splash guard installed. All electronics are contained within an explosion-proof housing so that the IR400’s detector information can be processed locally. Configurations with analogue output, Modbus and HART are also available.
IR400-0-01-1-2-0-1-0 IR400 point IR gas detector, 0-20 mA, methane, splash guard w/screen, aluminium housing
Replacement Infrared Sensors
IR400-0-01-2-2-0-1-0 = IR400, stainless steel, Methane
IR400-0-02-2-2-0-1-0 = IR400, stainless steel, Propane
IR400-0-04-2-2-0-1-0 = IR400, stainless steel, Hexane
IR400-0-05-2-2-0-1-0 = IR400, stainless steel, Pentane
IR400-0-06-2-2-0-1-0 = IR400, stainless steel, Ethylene
IR400-0-07-2-2-0-1-0 = IR400, stainless steel, Butane
IR400-0-08-2-2-0-1-0 = IR400, stainless steel, Ethane
IR400-0-13-2-2-0-1-0 = IR400, stainless steel, Methane, IECEx
IR400-0-14-2-2-0-1-0 = IR400, stainless steel, Propane, IECEx
IR400-0-15-2-2-0-1-0 = IR400, stainless steel, Hexane, IECEx
IR400-0-16-2-2-0-1-0 = IR400, stainless steel, Pentane, IECEx
IR400-0-17-2-2-0-1-0 = IR400, stainless steel, Butane, IECEx
IR400-0-18-2-2-0-1-0 = IR400, stainless steel, Ethane, IECEx
IR400-0-22-2-2-0-1-0 = IR400, stainless steel, Ethylene, IECEx
Calibration Equipment
32554-1 = CALIBRATION CUP IR400
1400270-2 = HARDWARE KIT – IR400 (contains 922-022 regulator, tubing,
32554-1 cal cup)
1400272-1 = Hardware Kit, Passive Catalytic Bead
Junction Boxes
31305-1 = JUNCTION BOX w/SWITCH, CSA/FM, AL
31305-2 = JUNCTION BOX w/o SWITCH, CSA/FM, AL
31305-3 = JUNCTION BOX w/SWITCH, CSA/FM, SST
31305-4 = JUNCTION BOX w/o SWITCH, CSA/FM, SST
31305-5 = JUNCTION BOX w/o SWITCH, ATEX/IECEx, SST, ADMA, GREY
31305-6 = JUNCTION BOX w/o SWITCH, ATEX/IECEx, AL
31305-7 = JUNCTION BOX w/o SWITCH, ATEX/IECEx, SST
31421-5 = ASSEMBLY, EUROPEAN, STANDARD JUNCTION BOX W/SWITCH, SST
31421-6 = ASSEMBLY, EUROPEAN, STANDARD JUNCTION BOX w/out SWITCH
| Parameter | Specification |
|---|---|
| Detector Type | Infrared absorption type |
| Measuring Range |
0 to 100% LEL 0 to 100% by volume (methane only) |
| Gases | Methane, propane, ethane, ethylene, butane, hexane, pentane, benzene. Consult factory for other gases. |
| Detector Life | Greater than 5 years |
| Accuracy @ 25°C |
±3% LEL at ≤ 50% LEL reading ±5% LEL at > 50% LEL reading |
| Zero Drift | < 2% per year |
| Response Time with Splash Guard |
T50 ≤ 1.5 s T60 ≤ 1.5 s T90 ≤ 3 s Except ethylene where T60 ≤ 2 s and T90 ≤ 4 s |
| Readout / Relay Display Modules | DC110, TA102A, IR4000 display, and relay alarms |
| Accessories | Junction box, duct mount junction box, calibration cup, flow block, splash guard, rain guard, portable purge calibrator |
| Classification |
Class I, Zone 1, IIB + H2 (Ta = -40°C to +75°C) Ex d, IIB + H2 T5 Gb Ex tb IIIC, T100°C Db, IP66 (Ta = -60°C to +75°C) |
| Warranty | Two years |
| Approvals |
ATEX, IECEx, MED, DNV GL, CE FM 6310, 6320 and CSA 22.2 No. 152 EN 60079-29-1 Performance Approved HART Registered, SIL 3 Suitable FM Certified to IEC 61508 |
| Environmental Specifications | |
| Operating Temperature Range |
FM, CSA, GOST-R: -40°F to +167°F (-40°C to +75°C) ATEX, IECEx: -76°F to +167°F (-60°C to +75°C) Ethylene: -40°F to +140°F (-40°C to +60°C) |
| Storage Temperature Range | -58°F to +185°F (-50°C to +85°C) |
| Operating Humidity Range | 10% to 95% RH, non-condensing |
| Electrical Specifications | |
| Input Power | 20-36 VDC @ 200 mA max. (24 VDC nominal) |
| Analog Signal | 0-21.7 mA (600 ohms max.) |
| EMC | Complies with EN 50270, EN 61000-6-4 |
| Cable Requirements |
Max. distance between IR400 and power source @ 24 VDC nominal
(20 ohm loop resistance): 14 AWG (2.0 mm²) – 3600 ft (1100 m) Max. distance for analog output (500 ohms max): 14 AWG (2.0 mm²) – 9000 ft (2740 m) |
| Baud Rate | 2400, 4800, 9600, or 19200 BPS |
| HART (Optional) |
HART 6, HART Device Descriptor available. AMS aware |
| Wireless Communication | Available with ELPRO Technologies wireless devices |
| Mechanical Specifications | |
| Diameter | 2.9" (74 mm) |
| Length | 8.87" (225 mm) |
| Weight – Aluminum | 3 lbs (1.35 kg) |
| Weight – Stainless Steel | 6 lbs (2.7 kg) |
| Mounting | ¾" NPT |
| Ingress Protection | Type 4X, IP66 |
| Housing | Aluminum 6061-T6 alloy or 316 stainless steel |
| Standard Configuration |
IR400-0-01-1-2-0-1-0 Methane, 4-20 mA, Modbus, aluminum, splash guard with screen, no junction box |
Get in touch with us to see how we can help you with your project