General Monitors IR400 Point IR Gas Detector

  1. Home
  2. Products

General Monitors IR400 Point IR Gas Detector

The IR400 Infrared (IR) Point Detector is a hydrocarbon gas detector that continuously monitors combustible gases and vapours within the lower explosive limit (LEL) and provides alarm indication.

It features an industry-leading response time of less than 3 seconds, even with a splash guard installed. All electronics are contained within an explosion-proof housing so that the IR400’s detector information can be processed locally. Configurations with analogue output, Modbus and HART are also available.

Features

  • Multiple communication outputs provide complete status and control capability in the control room.
  • Dirty optics indication discriminates between true fault and cleaning requirements.
  • Fast calibration times reduce the amount of calibration gas required, which lowers maintenance time & costs.
  • Industry-leading speed & response: T90 ≤ 3 seconds, even with a splash guard installed.

Order Information

IR400-0-01-1-2-0-1-0 IR400 point IR gas detector, 0-20 mA, methane, splash guard w/screen, aluminium housing

Replacement Infrared Sensors

IR400-0-01-2-2-0-1-0 = IR400, stainless steel, Methane
IR400-0-02-2-2-0-1-0 = IR400, stainless steel, Propane
IR400-0-04-2-2-0-1-0 = IR400, stainless steel, Hexane
IR400-0-05-2-2-0-1-0 = IR400, stainless steel, Pentane
IR400-0-06-2-2-0-1-0 = IR400, stainless steel, Ethylene
IR400-0-07-2-2-0-1-0 = IR400, stainless steel, Butane
IR400-0-08-2-2-0-1-0 = IR400, stainless steel, Ethane
IR400-0-13-2-2-0-1-0 = IR400, stainless steel, Methane, IECEx
IR400-0-14-2-2-0-1-0 = IR400, stainless steel, Propane, IECEx
IR400-0-15-2-2-0-1-0 = IR400, stainless steel, Hexane, IECEx
IR400-0-16-2-2-0-1-0 = IR400, stainless steel, Pentane, IECEx
IR400-0-17-2-2-0-1-0 = IR400, stainless steel, Butane, IECEx
IR400-0-18-2-2-0-1-0 = IR400, stainless steel, Ethane, IECEx
IR400-0-22-2-2-0-1-0 = IR400, stainless steel, Ethylene, IECEx

Calibration Equipment

32554-1 = CALIBRATION CUP IR400
1400270-2 = HARDWARE KIT – IR400 (contains 922-022 regulator, tubing, 32554-1 cal cup)
1400272-1 = Hardware Kit, Passive Catalytic Bead

Junction Boxes

31305-1 = JUNCTION BOX w/SWITCH, CSA/FM, AL
31305-2 = JUNCTION BOX w/o SWITCH, CSA/FM, AL
31305-3 = JUNCTION BOX w/SWITCH, CSA/FM, SST
31305-4 = JUNCTION BOX w/o SWITCH, CSA/FM, SST
31305-5 = JUNCTION BOX w/o SWITCH, ATEX/IECEx, SST, ADMA, GREY
31305-6 = JUNCTION BOX w/o SWITCH, ATEX/IECEx, AL
31305-7 = JUNCTION BOX w/o SWITCH, ATEX/IECEx, SST
31421-5 = ASSEMBLY, EUROPEAN, STANDARD JUNCTION BOX W/SWITCH, SST
31421-6 = ASSEMBLY, EUROPEAN, STANDARD JUNCTION BOX w/out SWITCH

Parameter Specification
Detector Type Infrared absorption type
Measuring Range 0 to 100% LEL
0 to 100% by volume (methane only)
Gases Methane, propane, ethane, ethylene, butane, hexane, pentane, benzene. Consult factory for other gases.
Detector Life Greater than 5 years
Accuracy @ 25°C ±3% LEL at ≤ 50% LEL reading
±5% LEL at > 50% LEL reading
Zero Drift < 2% per year
Response Time with Splash Guard T50 ≤ 1.5 s
T60 ≤ 1.5 s
T90 ≤ 3 s

Except ethylene where T60 ≤ 2 s and T90 ≤ 4 s
Readout / Relay Display Modules DC110, TA102A, IR4000 display, and relay alarms
Accessories Junction box, duct mount junction box, calibration cup, flow block, splash guard, rain guard, portable purge calibrator
Classification Class I, Zone 1, IIB + H2 (Ta = -40°C to +75°C)
Ex d, IIB + H2 T5 Gb
Ex tb IIIC, T100°C Db, IP66
(Ta = -60°C to +75°C)
Warranty Two years
Approvals ATEX, IECEx, MED, DNV GL, CE
FM 6310, 6320 and CSA 22.2 No. 152
EN 60079-29-1 Performance Approved
HART Registered, SIL 3 Suitable
FM Certified to IEC 61508
Environmental Specifications
Operating Temperature Range FM, CSA, GOST-R: -40°F to +167°F (-40°C to +75°C)
ATEX, IECEx: -76°F to +167°F (-60°C to +75°C)
Ethylene: -40°F to +140°F (-40°C to +60°C)
Storage Temperature Range -58°F to +185°F (-50°C to +85°C)
Operating Humidity Range 10% to 95% RH, non-condensing
Electrical Specifications
Input Power 20-36 VDC @ 200 mA max. (24 VDC nominal)
Analog Signal 0-21.7 mA (600 ohms max.)
EMC Complies with EN 50270, EN 61000-6-4
Cable Requirements Max. distance between IR400 and power source @ 24 VDC nominal (20 ohm loop resistance):
14 AWG (2.0 mm²) – 3600 ft (1100 m)

Max. distance for analog output (500 ohms max):
14 AWG (2.0 mm²) – 9000 ft (2740 m)
Baud Rate 2400, 4800, 9600, or 19200 BPS
HART (Optional) HART 6, HART Device Descriptor available.
AMS aware
Wireless Communication Available with ELPRO Technologies wireless devices
Mechanical Specifications
Diameter 2.9" (74 mm)
Length 8.87" (225 mm)
Weight – Aluminum 3 lbs (1.35 kg)
Weight – Stainless Steel 6 lbs (2.7 kg)
Mounting ¾" NPT
Ingress Protection Type 4X, IP66
Housing Aluminum 6061-T6 alloy or 316 stainless steel