The FL4000H is obsolete and has been replaced by the FL5000 flame detector.
The General Monitors FL4000H is an advanced multi-spectrum flame detector designed to provide superior false alarm immunity with the widest field of view. The FL4000H employs a state-of-the-art multi-spectrum infrared (MSIR) sensor array with a sophisticated Neural Network Technology (NNT) system.
The FL4000H is designed to detect typical fires such as those produced by alcohol, n-heptane, gasoline, jet fuels and hydrocarbons. In addition, the FL4000H can see through dense smoke produced by diesel, rubber, plastics, lube oil, and crude oil fires.
The NNT flame discrimination algorithm classifies the output signals from the MSIR sensor array as either fire or non-fire. The MSIR/NNT combination is highly immune to false alarms caused by lightning, arc welding, hot objects, and other sources of radiation.
The FL4000H’s electronics are housed in a stainless steel explosion-proof enclosure. The detector is available with the following output configurations:
The serial communication port(s) allow 128 units (247 using repeaters) to be linked to a host computer using the Modbus RTU protocol. The communication registers provide alarm status, fault information, and other details for operating, troubleshooting, or programming the unit.
The COPM (Continuous Optical Path Monitoring) self-test checks optical path integrity (window cleanliness) and the detector’s electronic circuitry every two minutes.
10242703 = FL4000H to FL5000 Upgrade Kit
712005-1 = optical assembly w/configuration kit FL4000h
712005-2 = optical assembly hart w/configuration kit FL4000h
712005-3 = optical assembly hart 1.25 w/configuration kit FL4000h
71281-1a = field wiring board for FL4000h w/relays
71281-2a = field wiring board for FL4000h w/o relays
| System Specifications | |
| SPECTRAL RANGE | 2-5 microns (IR) |
| MAXIMUM RANGE | 230 ft. (70 m)* |
| TYP. RESPONSE TIME | ≤ 10 s |
| MIN. ARC WELDING IMMUNITY DISTANCE | 5-15 ft. (1.5-4.6 m) depending on rod |
| MAX. FIELD OF VIEW | 100° @ 100 ft; 90° @ 210 ft.† |
| ACCESSORIES | Test lamp, mounting bracket |
| CLASSIFICATION |
Class I, Div 1, Groups B, C, D Class II, Div 1, Groups E, F, G Class III, Type 6P Ex d IIC T5 Gb Ex tb IIIC, T100°C Db, IP66/67 HART Registered SIL 3 Suitable (FM) |
| WARRANTY | Two years |
| APPROVALS | CSA, FM, ULC, ATEX, IECEx, EN 54-10, MED, DNV-GL, VNIIPO, GOST, Inmetro, CE |
| Environmental Specifications | |
| OPERATING/STORAGE TEMPERATURE RANGE | -40° F to +176° F (-40° C to +80° C) |
| OPERATING HUMIDITY RANGE | 10% to 95% RH, non-condensing |
| Mechanical Specifications | |
| HOUSING | 316 stainless steel |
| HEIGHT | 4.3” (109 mm) |
| DIAMETER |
5.4” (137 mm) base 3.5” (89 mm) optical housing |
| WEIGHT | 7.9 lbs (3.6 kg) |
| MOUNTING | Stainless steel mounting bracket |
| CABLE ENTRY | 2 x ¾” NPT |
| Electrical Specifications | |
| INPUT POWER | 20-36 VDC 24 VDC @ 150 mA (4.4 W) |
| ANALOG SIGNAL |
0-20 mA (600 ohms maximum) 3.5-20 mA (HART) |
| FAULT MODE | 0 mA to 0.2 mA |
| TEST MODE | 1.5 mA, ± 0.2 mA |
| COPM FAULT | 2 mA, ± 0.2 mA |
| READY MODE | 4.3 mA, ± 0.2 mA |
| WARN MODE | 16 mA, ± 0.2 mA |
| ALARM MODE | 20 mA, ± 0.2 mA |
| RELAY CONTACT RATING | 8A @ 250 VAC, 8A @ 30 VDC resistive maximum |
| EMC | Complies with EN 61000-6-4 and EN 50130-4 |
| RS-485 OUTPUT | Modbus RTU, suitable for linking up to 128 units and 247 units with repeaters |
| BAUD RATE | 2400, 4800, 9600, 19200, or 38400 bit/s |
| HART | HART 6, HART Device Description Language available. AMSaware |
| STATUS INDICATORS | Two LEDs with status and fault cues |
| FAULT MONITORING | RAM, EPROM and EEPROM checksum errors, optics failure/blockage and low supply voltage |
| CABLE REQUIREMENTS |
3 wire shielded cable minimum configuration Maximum distance between FL4000H and power source or remote sensor @ 24 VDC nominal (20 ohm loop): 14 AWG – 3,000 ft (930 m) Maximum distance for analog output (250 ohms max): 14 AWG – 9,000 ft. (2,750 m) |