The Detcon model TP-524D by Teledyne is a “Smart” gas detection sensor designed to detect and monitor H2S in the air over the ranges of 0-20 ppm, 0-50 ppm, and 0-100 ppm using a proprietary solid-state metal oxide semiconductor technology.
This innovative design offers several advantages, including longer sensor life and better temperature and humidity performance. Model TP-524D features Detcon’s MicroSafe intelligent electronics, non-intrusive operator interface and comprehensive fault diagnostics.
The sensor transmitter features an advanced universal design that fits all existing Detcon MOS H2S sensors dating back more than 20 years. The sensor assembly includes a MOS detector in a stainless steel housing, a base connector board, an explosion-proof enclosure (available in aluminium or stainless steel), a plug-in control transmitter circuit, and a splashguard with an integral calibration port. The packaging is Explosion Proof (Class I, Division 1, Groups B, C, D).
Model TP-524D is equipped with a standard analogue 4-20 mA current signal equivalent to the sensor range of detection, self-adjusting zero and span, and LED indicators for fault and calibration status. A HART communications option is also available. An industry-leading 10-year conditional warranty supports Detcon’s solid-state MOS sensor.
| Part Number | Description |
|---|---|
| 965-015420-100 | TP-524D Solid State MOS H2S Sensor Assembly in Alum Condulet |
| 965-01542B-100 | TP-524D-316SS Solid State MOS H2S Sensor Assembly in SS Condulet |
| 9H5-015420-100 | TP-524D-HRT MOS H2S Sensor Assembly with HART Alum Condulet |
| 9H5-01542B-100 | TP-524D-HRT MOS H2S Sensor Assembly with HART SS Condulet |
| Part Number | Description |
|---|---|
| 943-000000-000 | Calibration Sleeve / Wind Guard (for use with splash guard) |
| 960-202200-000 | Condensation prevention packet (replace annually) |
| 437-500000-000 | Stainless steel tag |
| 943-004223-000 | 2″ pipe mount with sun shade |
| 943-004221-000 | Sensor Mounting Plate for 2″ pipe |
| 943-002273-000 | Harsh location dust guard (fits 1.5 x 18 thread) |
| 033-003238-000 | Replacement filter for dust guard (pack of 20) |
| 943-002274-000 | Hazardous location dust guard (7/8) for TP series sensors |
| 943-003236-000 | Replacement filter for harsh location dust guard (pack of 20) |
| 943-003436-000 | Harsh location water guard (fits standard splash guards) |
| 897-850000-010 | Aluminum junction box with solid lid |
| 897-850901-010 | Aluminum junction box with lens cover |
| 897-850000-316 | Stainless steel junction box with solid cover |
| 897-850901-316 | Stainless steel junction box with lens cover |
| 943-121747-SS5 | Stainless steel flow-through adapter |
| Part Number | Description |
|---|---|
| 399-800000-000 | Solid State MOS H2S Sensor in Stainless Steel Housing |
| 925-0154D0-100 | Plug-in transmitter control module (Model TP-524D) |
| 925-015HD0-100 | Plug-in transmitter module (Model TP-524D) with HART |
| 500-005230-100 | Standard connector board (Model series 400 & 500 sensors) |
| 326-000000-000 | Replaceable sintered stainless steel flame arrestor |
| 600-610000-000 | Sensor splash guard with integral calibration port |
| 943-000006-038 | Calibration adapter TP |
| 975-000020-891 | Sensor duct mount kit TP |
| 943-002274-000 | Harsh location dust guard (fits 7/8 x 14 thread) |
| 033-003236-000 | Harsh location dust guard replacement filter |
| Sensor Type | Continuous Diffusion/Adsorption, CHEMFET Solid State Metal Oxide Semiconductor |
| Sensor Life | 5 to 10 Years Typical |
| Measurement Range | 0–20 ppm, 0–50 ppm, 0–100 ppm |
| Accuracy / Repeatability | ±10% of Reading or ±2 ppm (Whichever is Greater) |
| Response / Clearing Time | T50 < 30 Seconds; T90 < 60 Seconds |
| Outputs |
Linear 4–20 mA DC Optional HART Communication |
| Electrical Classification |
Explosion Proof CSAus: Class I, Division 1, Groups B, C & D (Tamb = -25°C to +40°C) Class I, Zone 1, Group IIB+H2 cCSA: Class I, Division 1, Groups B, C & D (Tamb = -40°C to +40°C) Class I, Zone 1, Group IIB+H2 FM: Class I, Division 1, Groups B, C & D (Tamb = -40°C to +60°C) Complies with ANSI/ISA 92.00.01-2010 ATEX: Ex d IIB+H2 T4 (Tamb = -40°C to +60°C) |
| Ingress Protection | NEMA 4X, IP66 |
| Warranty |
Plug-in Detector: 10-Year Conditional Warranty Transmitter: 2-Year Warranty |
| Operating Temperature Range |
Canada: -40°C to +40°C (-40°F to 104°F) USA: -25°C to +40°C (-13°F to 104°F) |
| Storage Temperature Range | -35°C to +55°C (-31°F to +131°F) |
| Operating Humidity Range | 5–100% RH, Non-condensing |
| Operating Pressure Range | Atmospheric ±10% |
| Dimensions |
254 × 155 × 109 mm (H × W × D) 10" × 6.1" × 4.3" (Including Splashguard) |
| Mounting Holes (J-Box) | 140 mm (5.5") Centre-to-Centre |
| Weight |
2.72 kg (6 lbs) with Aluminum J-Box 4.08 kg (9 lbs) with Stainless Steel J-Box |
| Power Input | 12–28 VDC |
| Power Consumption |
Normal Operation: 68 mA (<1.7 W) Maximum: 85 mA (2 W) |
| RFI / EMI Protection | Complies with EN 50270 |
| Analog Output |
Linear 4–20 mA DC (1,000 Ω Max Loop Load @ 24 VDC) 0 mA – All Fault Diagnostics 2 mA – In Calibration 4–20 mA – 0–100% Full Scale 22 mA – Over-range Condition |
| Status Indicators |
4-Digit LED Display with Gas Concentration Full-Script Menu Prompts for AutoSpan, Setup Options and Fault Reporting LEDs for Fault and Calibration |
| Faults Monitored |
Heater, Loop, Input Voltage, Sensor, Processor, Memory, Calibration |
| Cable Requirements |
Power / Analog: 3-Wire Shielded Cable Maximum Distance: 13,300 ft (4,054 m) with 14 AWG |
| I/O Protection | Over-voltage, Miswiring, EMI/RFI Immunity |
Get in touch with us to see how we can help you with your project