The Detcon model FP-624D by Teledyne is a “Smart” gas detection sensor designed to detect and monitor combustible gas in the air over the range of 0-100% LEL (lower explosive limit) using matched-pair catalytic bead technology.

Model FP-624D features Detcon’s MicroSafeTM intelligent electronics, non-intrusive operator interface and comprehensive fault diagnostics. The sensor transmitter features an advanced universal design that fits all existing Detcon matched-pair catalytic bead sensors, dating back over 20 years.

The sensor assembly includes the detector in a stainless steel housing, a base connector board, an explosion-proof enclosure (available in aluminium or stainless steel), a plug-in control transmitter circuit, and a splashguard with an integral cal port. The packaging is Explosion Proof (Class I, Division 1, Groups C & D).

Equipped with a standard analogue 4-20 mA current signal equivalent to the sensor range of detection, RS-485 serial communications port, two alarm relays and one fault relay, one-person remote calibration, self-adjusting zero and span, and LED indicators for fault, alarm, and calibration status. Detcon’s combustible gas sensor has an infinite shelf life and is supported by a 2-year warranty.

Features

  • Performance Certified to CSA 152 cCSAus for Class I, Division 1, Groups C & D.
  • Transmitter design fits all existing Detcon Catalytic Bead Sensors dating back 20 years.
  • Compatible with PLCs, SCADA, DCS, via 4-20 mA, and/or RS485, and/or alarm relays.
  • Sensor status and parameters are accessible via RS-485 (Modbus).
  • Menu programmable relays standard (two alarms plus fault).
  • Simple menu-driven calibration – less than 3 minutes.
  • LED display with LED indicators for FAULT and CAL status.
  • Plug-in field-replaceable transmitter.
  • Long sensor life: averaging +5 years in harsh offshore drilling/production environments.
  • High resistance to poisons such as sulfides, chlorides, silicon-based contaminants, etc.
  • Low power consumption (less than 3.5 watts versus 8+ watts on competitive brands).
  • Extensive Fault diagnostics.

Applications

  • Oil and Gas Drilling Rigs
  • Oil and Gas Production Sites
  • Offshore Production Platforms
  • FPSOs
  • LNG/CNG Plants
  • Refining and Petrochemical
  • Pulp and Paper Mills
  • Waste Water Treatment Plants

Order Information

Sensor Assemblies

Part Number Description
966-524520-100 FP-624D Catalytic Combustible Gas Sensor Assembly Alum condulet
966-52452B-100 FP-624D Catalytic Combustible Gas Sensor Assembly 316SS condulet

Accessories

Part Number Description
943-000000-000 Calibration Sleeve / Wind Guard (for use with splash guard)
960-202200-000 Condensation prevention packet (replace annually)
437-500000-000 Stainless steel tag
943-004223-000 2″ pipe mount with sun shade
943-004221-000 Sensor Mounting Plate for 2″ pipe
943-002273-000 Harsh location dust guard (fits 1.5 x 18 thread)
033-003238-000 Replacement filter for dust guard (pack of 20)
943-002274-000 Hazardous location dust guard (7/8) for TP series sensors
943-003236-000 Replacement filter for harsh location dust guard (pack of 20)
943-003436-000 Harsh location water guard (fits all standard splash guards)
897-850000-010 Aluminum junction box with solid lid
897-850901-010 Aluminum junction box with lens cover
897-850000-316 Stainless steel junction box with solid cover
897-850901-316 Stainless steel junction box with lens cover
943-121747-SS5 Stainless steel flow-through adapter
Sensor Type Matched-pair catalytic bead
Sensor Life 3 to 5 years typical
Measurement Range 0–100% LEL (Lower Explosive Limit)
Accuracy / Repeatability ±3% (0–50% LEL)
±5% (50–100% LEL)
Response / Clearing Time T50 < 10 seconds; T90 < 30 seconds
Zero Drift < 5% per year
Outputs Linear 4–20 mA DC
Optional HART
3 Relays (Alarm 1, Alarm 2 & Fault), Contacts Rated 5 A
Electrical Classification Explosion Proof

CSAus: Class I, Division 1, Groups C, D (Tamb = -25°C to +40°C)
Class I, Zone 1, Group IIB

cCSA: Class I, Division 1, Groups C, D (Tamb = -40°C to +40°C)
Class I, Zone 1, Group IIB
Performance Approvals CSA C22.2 #152
Safety Approvals cCSAus
Ingress Protection NEMA 4X, IP66
Warranty Sensor: 2 Years
Transmitter: 2 Years
Operating Temperature Range Canada: -40°C to +40°C (-40°F to 104°F)
USA: -25°C to +40°C (-13°F to 104°F)
Storage Temperature Range -40°C to +75°C (-40°F to +167°F)
Operating Humidity Range 0–99% RH, Non-condensing
Operating Pressure Range Atmospheric ±10%
Dimensions 254 × 155 × 109 mm (H × W × D)
10" × 6.1" × 4.3" (Including Splashguard)
Mounting Holes (J-Box) 140 mm (5.5") Center-to-Center
Weight 2.72 kg (6 lbs) with Aluminum J-Box
4.08 kg (9 lbs) with Stainless Steel J-Box
Power Input 12–28 VDC
Power Consumption Normal Operation: 68 mA (<1.7 W)
Maximum: 87 mA (2 W)
RFI / EMI Protection Complies with ISO 92.0.01
Analog Output Linear 4–20 mA DC (1,000 Ω max loop load @ 24 VDC)
0 mA – All Fault Diagnostics
2 mA – In Calibration
4–20 mA – 0–100% Full Scale
22 mA – Over-range Condition
Status Indicators 4-Digit LED Display with Gas Concentration
Full-Script Menu Prompts for AutoSpan, Setup Options & Fault Reporting
LEDs for Alarm 1, Alarm 2, Fault & Calibration
Relay Outputs Alarm 1, Alarm 2 & Fault
5 A @ 250 VAC
5 A @ 30 VDC
Faults Monitored Loop, Input Voltage, Zero Sensor, Processor, Memory, Calibration
Cable Requirements Power / Analog: 3-Wire Shielded Cable
Maximum Distance: 13,300 ft (4,054 m) with 14 AWG
Serial Output 2-Wire Twisted-Pair Shielded Cable for RS-485 Installations
Maximum Distance: 4,000 ft (1,219 m) to Last Sensor
I/O Protection Over-voltage, Miswiring, EMI/RFI Immunity