The SMART 3G-D3 Gas Detector with Infrared sensor is designed to meet industrial requirements; the enclosure is explosion-proof and can be installed in ATEX Zone 2 and, when equipped with a dust adapter, in Zone 22.
The sensing element is placed in the stainless steel head with a 47.5 mm diameter. The infrared sensors employed for flammable and refrigerant gas detection are poison-free, with high accuracy and a long lifetime.
The gas detector has a 12-24 Vdc power supply, a standard 4-20 mA 3-wires output, and three relays. Optionally, the SMART3G-D3 can be equipped with serial RS485 communication.
The enclosure has dimensions 106 x 160 x 81 mm; on the upper side, there’s a M20 cable gland. The SMART3G-D3 features a 7-segment display for real-time concentration visualization and Hall effect sensors for non-intrusive field calibration.
SMART3G-D3 is SIL2 hardware and SIL3 software with a redundant system; the hardware is SIL3.
| Sensor Part Number | Description |
|---|---|
| SMART3G-D3 – FLAMMABLE GAS (Infrared sensor) | |
| S2625ME | METHANE detector, 4-20 mA, 0-100% LFL |
| S2601PR | PROPANE detector, 4-20 mA, 0-100% LFL |
| S2601BU | BUTANE detector, 4-20 mA, 0-100% LFL |
| S2601GP | LPG detector, 4-20 mA, 0-100% LFL |
| S4434R454B | R454B detector, 4-20 mA, 0-100% LFL |
| S4828R454C | R454C detector, 4-20 mA, 0-100% LFL |
| S3426R32 | R32 DIFLUOROMETHANE detector, 4-20 mA, 0-100% LFL |
| S3430R1234YF | R1234yf detector, 4-20 mA, 0-100% LFL |
| S3435R1234ZE | R1234ze detector, 4-20 mA, 0-100% LFL |
| SMART3G-D3 – CO2 (Infrared sensor) | |
| S2631CO2 | CARBON DIOXIDE (CO2) detector, 0-2% Vol., 4-20 mA |
| S2632CO2 | CARBON DIOXIDE (CO2) detector, 0-5% Vol., 4-20 mA |
| S2447CO2 | CARBON DIOXIDE (CO2) detector, 0-30% Vol., 4-20 mA |
| S2448CO2 | CARBON DIOXIDE (CO2) detector, 0-5000 ppm, 4-20 mA |
| S2633CO2 | CARBON DIOXIDE (CO2) detector, 0-100% Vol., 4-20 mA |
| SMART3G-D3 – SF6 and REFRIGERANT GASES (Infrared sensor) | |
| S3943R32 | R32 detector, 0-2000 ppm, 4-20 mA |
| S3597R134A | R134a detector, 0-2000 ppm, 4-20 mA |
| S3600SF6 | SF6 detector, 0-2000 ppm, 4-20 mA |
| S3651R125 | R125 detector, 0-2000 ppm, 4-20 mA |
| S3652R1234YF | R1234yf detector, 0-2000 ppm, 4-20 mA |
| S3947R1234ZE | R1234ze detector, 0-2000 ppm, 4-20 mA |
| S3653R404A | R404A detector, 0-2000 ppm, 4-20 mA |
| S3654R407A | R407A detector, 0-2000 ppm, 4-20 mA |
| S3919R407F | R407F detector, 0-2000 ppm, 4-20 mA |
| S3922R449A | R449 detector, 0-2000 ppm, 4-20 mA |
| S3655R507A | R507A detector, 0-2000 ppm, 4-20 mA |
| S3672R410A | R410A detector, 0-2000 ppm, 4-20 mA |
| S3951R417A | R417A detector, 0-2000 ppm, 4-20 mA |
| S3955R448 | R448 detector, 0-2000 ppm, 4-20 mA |
| ACCESSORIES | |
| STS/CSW+ | Calibration software for SMART3G, SMART3NC & SMART3R detectors including USB key, USB/RS485 converter and STS/IDI card. Allows alarm threshold changes, range setup, and Zero/Span/4-20 mA calibration via user-friendly interface. |
| STS/IDI | Plug-in interface for RS485 serial communication suitable for SMART3G |
| STGD/AD3 | Adapter for all sensor heads (except S2096__ & S2097__) to upgrade protection from G to GD |
| Sensor | |
| Application | Industrial area, ATEX Zone 2 e Zone 22 (when equipped with dust adapter, optional) |
| Sensing element | Infrared |
| Predicted sensor lifetime | >5 years |
| Gas detected | Flammable, refrigerant and CO2 |
| Full scale |
0 – 100% LFL flammable gas 0 – 2000 ppm refrigerant gas 0-2%Vol; 0-5%Vol; 0-30%Vol; 0-100%Vol CO2 |
| Electrical data | |
| Power supply | 12-24 Vdc |
| Output | Analogue 4-20 mA output; 3 relays; serial RS485 output (optional) |
| Maximum dissipated power | 5.4 W |
| Relays contact ratings | 1.0 A at 24 Vdc |
| Optical indications | 7-segment display, 5 status LED and 4 intelligent LED |
| Acoustic indications | – |
| Hall effect sensor | Three sensors for calibration by magnet |
| Environmental conditions | |
| Storage temperature | -40 / +85°C |
| Operating temperature | -40 / +60°C |
| Operating humidity | 0 / 90% RH |
| External case | |
| Material |
Enclosure: Aluminium Sensor head: stainless steel |
| Protection mode |
Ex e: Increased safety protection mode Ex nC: Enclosed equipment protection mode Ex d : Explosion proof enclosure Ex t : Equipment dust ignition protection by enclosure (when equipped with dust adapter, optional) |
| Dimensions | 106 x 160 x 81 mm |
| Weight | 1210 g |
| Cable entries | 1 x M20 |
| IP grade | IP55 (certification pending) |
| Compliance | |
| EMC | EN 61000-6-3:2007 + A1:2011; EN 50270:2015 |
| ATEX |
ATEX directive 2014/34/EU (certification pending) EN IEC 60079-0:2018 EN 60079-1:2014 EN 60079-7:2015 EN 60079-15:2010 EN 60079-31:2014 |
| SIL |
EN 61508:2010 Parts 1, 2, 3, 4, 5, 6, 7 EN50402:2017 |
Get in touch with us to see how we can help you with your project