SMART3-R is developed to detect gases in non-classified areas, such as machinery rooms and laboratories.
Due to the optimal performance in these applications, an electrochemical cell detects toxic gases. Four smart LEDs illuminate the transparent ring to describe the detector status, and an internal buzzer is activated in alarm and fault conditions.
The SMART3-R gas detector has a standard 12-24 Vdc power supply, but a 220 Vac version can be supplied. The gas detector has three relay outputs, an RS485 serial communication and an analogue 4-20 mA output (not in the 220 Vac version).
The polycarbonate case has a global size of 130 x 130 x 74 mm. The box has two entries with M20 cable glands. Pre-formed guides can be drilled on the sides to add up to 6 M16 cable glands.
The gas detector can have a remote head connected with a RJ12 6P6C cable.
| Sensor Part Number | Description |
|---|---|
| SMART 3-R – TOXIC GASES (Electrochemical cell) | |
| S4593O2 | OXYGEN (O2) detector, 0-25% Vol., 4-20 mA |
| S4595CO | CARBON MONOXIDE (CO) detector, 0-500 ppm, 4-20 mA |
| S4597AM | AMMONIA (NH3) detector, 0-100 ppm, 4-20 mA |
| S4598AM | AMMONIA (NH3) detector, 0-200 ppm, 4-20 mA |
| S4599AM | AMMONIA (NH3) detector, 0-1000 ppm, 4-20 mA |
| S4634CL | CHLORINE (Cl2) detector, 0-20 ppm, 4-20 mA |
| S4601HS | HYDROGEN SULPHIDE (H2S) detector, 0-50 ppm, 4-20 mA |
| S4630SD | SULPHUR DIOXIDE (SO2) detector, 0-20 ppm, 4-20 mA |
| S4632ND | NITROGEN DIOXIDE (NO2) detector, 0-20 ppm, 4-20 mA |
| ACCESSORIES for SMART 3-R & SMART 3-R LITE | |
| STS/IDI | Plug-in RS485 interface enables SMART3NC detectors to communicate in Modbus protocol with MULTISCAN++S1, MULTISCAN 8+ & STPL4+D control panels |
| STS/CKD+ | Enhanced calibration keypad with 7-digit display and SD-CARD slot for Zero, Span, and 4-20 mA adjustments, with firmware update capability via SD card |
| Sensor | |
| Application | Machinery rooms, laboratories and non-classified areas |
| Sensing element | Electrochemical cell |
| Predicted life sensor | 2 / 3 years |
| Gas detected | O2 [0-25% Vol], CO [0-500 ppm], SO2 [0-20 ppm], NH3 [0-100/200/1000 ppm], Cl [0-20 ppm], H2S [0-50 ppm], NO2 [0 – 20 ppm] |
| Electrical data | |
| Power supply | 12-24 Vdc or 90-240Vac |
| Signal output | 3 relays; RS485 serial output, 4-20 mA analogue output (only for 12-24 Vdc version) |
| Dissipated power | 60 mA at 24Vdc |
| Relays contact rating | 1.0 A at 30 Vdc |
| Optical indications | 4 smart LED |
| Acoustic indications | Buzzer 63 dB @1mt |
| Remote head cable | RJ12 6P6C |
| Environmental conditions | |
| Storage temperature | 0 / +20°C up to 6 months |
| Operating temperature | -30 / +50°C |
| Operating humidity | 15 / 90% RH non condensing |
| Compliance | |
| EMC | EN 61000-6-3:2007 + A1:201; EN 50270:2015 |
| Electrical safety (90-240 Vac version) | EN 61010-1: 2010 / A1: 2019 |
| Refrigeration Standards | EN 378-3; EN 14624; EN 50676; IEC 60335-2-40 Annex LL; ISO 5149-3; F-Gas Regulation |
| External case | |
| Material | Polycarbonate |
| Dimensions |
Box: 120 x 120 x 52 mm Cover: 130 x 130 x 22 mm Remote head box: 106 x 106 x 56 mm Maximum length of remote head’s cable: 5 m |
| Weight |
Detector: 450 g Remote head: 300 g |
| Cable entry |
2 entries with M20 cable glands 6 optional entries for M16 cable glands |
| IP Grade | IP42 |
Get in touch with us to see how we can help you with your project