Crowcon GM Addressable Controllers

  1. Home
  2. Products

Crowcon GM Addressable Controllers

Crowcon’s range of addressable gas detection controllers are easy to configure and are very user-friendly.

There are 3 controller options with different channel input variables.

Local non-intrusive operation & display with simultaneous live reading display and alarm functions via colour LCD display.

There is also a ‘direct to web page’ live feed communication feature for viewing or taking action remotely.

There are 3 addressable gas detection controller options with identical functionality but different channel input capabilities.

  • GM16: 1-16 Channel inputs
  • GM64: 1-64 Channel inputs
  • GM128: 1-128 Channel inputs

All are available as 19” rack mounted, with enclosure options available for GM16 & GM64.

Our addressable gas detection controllers are modular and can be configured according to requirements. To reduce complexity and cost, only include what is needed for the application.

Capability

  • LCD display provides simultaneous visibility for all live channel readings and alarm functions in system setup (up to 64 input variables)
  • 4-20ma analogue & RS-485 Modbus communications are standard, and HART-compatible communications are enabled.
  • Direct to web page live feed communication for remote viewing and acknowledgement actions
  • Flexible configuration options allow the ability to name controller, name zones, set the alarm & relay setpoints
  • Ability to group channels into zoned areas

Functions

  • Main data screen – Displays all active channels on the same screen. Cells indicate alarm status by colour
  • Bar graph screen – Display 16 channels at a time, side scroll bar for clear coloured indicator for focused channel alarm status
  • 24-hour trend screen – Review 24-hour gas monitor trend for a single channel at a time
  • 3-minute trend screen – Review the most recent 30-minute trend for a single channel at a time
  • Zone screen – Display up to 8 active zones on a single screen. Individual channels within zone visibility


Part Number Description
Controller Type
GM Range of Addressable Controllers
No Power Supply
016ZS GM16 – 16 Channel Controller – Small Enclosure – No Power Supply
016ZF GM16 – 16 Channel Controller – Full Width 19″ Rack – No Power Supply
016ZH GM16 – 16 Channel Controller – Half Width 19″ Rack – No Power Supply
064ZS GM64 – 64 Channel Controller – Small Enclosure – No Power Supply
064ZL GM64 – 64 Channel Controller – Large Enclosure – No Power Supply
064ZF GM64 – 64 Channel Controller – Full Width 19″ Rack – No Power Supply
128ZF GM128 – 128 Channel Controller – Full Width 19″ Rack – No Power Supply
Low Power Supply (150W)
016LS GM16 – 16 Channel Controller – Small Enclosure – Low Power Supply (150W)
016LF GM16 – 16 Channel Controller – Full Width 19″ Rack – Low Power Supply (150W)
016LH GM16 – 16 Channel Controller – Half Width 19″ Rack – Low Power Supply (150W)
064LS GM64 – 64 Channel Controller – Small Enclosure – Low Power Supply (150W)
064LL GM64 – 64 Channel Controller – Large Enclosure – Low Power Supply (150W)
064LF GM64 – 64 Channel Controller – Full Width 19″ Rack – Low Power Supply (150W)
128LF GM128 – 128 Channel Controller – Full Width 19″ Rack – Low Power Supply (150W)
High Power Supply (600W)
016HS GM16 – 16 Channel Controller – Small Enclosure – High Power Supply (600W)
016HF GM16 – 16 Channel Controller – Full Width 19″ Rack – High Power Supply (600W)
016HH GM16 – 16 Channel Controller – Half Width 19″ Rack – High Power Supply (600W)
064HS GM64 – 64 Channel Controller – Small Enclosure – High Power Supply (600W)
064HL GM64 – 64 Channel Controller – Large Enclosure – High Power Supply (600W)
064HF GM64 – 64 Channel Controller – Full Width 19″ Rack – High Power Supply (600W)
128HF GM128 – 128 Channel Controller – Full Width 19″ Rack – High Power Supply (600W)
Parameter Specification
System Configuration Ability to name the controller
Create up to eight named zones
Choose how many channels are displayed simultaneously
Channel Configurations Choose alarm setpoints
Select data each channel displays
Relay Configurations Set values for high and low trips for each relay
Choose colour for set trip value
Set delays for each relay option
Copy Channel Copy and paste an already configured channel to a new channel to save time for multiple identical configurations
Configuration Upload / Download Configure remotely via device and download onto SD card
Inserting SD card into controller automatically uploads saved configuration
Small Enclosure
Enclosure Material Fibreglass
Dimensions 406.4 x 334.3 x 215.9 mm (16.00 x 13.16 x 8.50 ins)
Weight 7.7 Kg (17 lbs)
Ingress Protection NEMA 4X
Large Enclosure
Enclosure Material Fibreglass
Dimensions 612.4 x 687.3 x 241.6 mm (24.11 x 27.06 x 9.51 ins)
Weight 25 Kg (55 lbs)
Ingress Protection NEMA 4X
Rack Mount 19 inch rack mount option also available
Power Typical power use without detector heads is 20 to 50 Watts
Electrical Output 4-20mA 2 wire current sink
4-20mA 3 wire current source
RS-485 Modbus RTU
Relays 5 Amp 30 Volt
RJ45 network connection
Operating Temperature -20°C to +50°C
Humidity 0 to 90% non-condensing
Repeatability and Drift Digital channels – no controller variability
Analog channels – <1% FSD change over a 1 year period
Approvals May be used in a non-hazardous area as part of an intrinsically safe system
EMC Compliance CE marked